The server is under maintenance between 08:00 to 12:00 (GMT+08:00), and please visit later.
We apologize for any inconvenience caused
Login  | Sign Up  |  Oriprobe Inc. Feed
China/Asia On Demand
Journal Articles
Laws/Policies/Regulations
Companies/Products
Bookmark and Share
kong qi yuan re beng zai nong cun di qu ying yong xia de zhi re xing neng ce shi
Author(s): 
Pages: 34-36,41
Year: Issue:  10
Journal: Energy Conservation

Keyword:  节能减排空气源热泵供暖效果制热性能;
Abstract: 对空气源热泵散热器系统在农村地区冬季供暖效果和制热性能进行测试,结果表明:在室外平均温度-7.49℃以下,测试房间内温度在16.91~18.65℃;连续30min不停机测试下,空气源热泵机组制热平均性能系数为2.52.连续测试4d,机组温控器设定50℃情况下,热泵机组制热平均性能系数为2.19,热泵系统能效比为1.94.
Related Articles
No related articles found