Piping design scheme discussion of parallel cooling towers
Author(s): Zhang Ye, Tsinghua University
Pages: 29-
32
Year: 2016
Issue:
1
Journal: Heating Ventilating & Air Conditioning
Keyword: cooling tower; parallel; overflow; balance pipe; water level;
Abstract: In parallel cooling towers engineering projects,the common scheme is to install an electric valve in the water inlet of the tower linkage with the cooling water pump but not in the water outlet and set up balance pipes among the parallel towers,which meets the design specifications.In practically,when the inlet valve is switched off,water spills over from the opened tower whereas the closed tower receives water supplement.Investigates the reason and proposes suggestions by an analysis of specific case.
Citations
No citation found